Intake air conditioning device:
Air flow: the intake air conditioning device is 1000m3/h~4000m3/h;
Connection way: sealed connection or exposure connection through universal-inlet wind cover;
Applicable environment: less than 1000m, or custom-made for high altitude or high-space condition;
Ambient temperature range: 0-40 ºC(anti-freezing measures is required in below 0 ºC region );
Temperature adjustable range: 25-35 ºC         accuracy: ≤ ±1ºC
Humidity control precision: < ±5% r.h.
The humidity and pressure adjusting range can be custom-made according to specific requirement.
A system can supply for one, two or four bench testing, to save space.
 
Cooling tower parameter:
Cooling tower type: open or closed;
Applicable environment: less than 3000m, or custom-made for high altitude or high-space condition;
Ambient temperature range: 0-40 ºC(anti-freezing measures is required in below 0 ºC region );
Circulating water temperature: inlet and outlet of the water is 32 -37 ºC or 32-42 ºC. Model is optional.
Circulating water flow: 6-1000m³/h, model is optional.
Special requirements of equipment, such as wind-pressure resistance, earthquake-resistance, can be customized.

Water chilling device parameters:
Type: air-cooled, or water-cooled;
Applicable environment:
    Less than 3000m, or custom-made for high altitude or high-space condition;
    Ambient temperature range: 0~35ºC
    Required external circulating water temperature: inlet and outlet of the water 30 ~ 35 ºC
Water chilling device capability:
    Chilling water temperature: 7~12ºC,-5~0ºC,-15~-5ºC,
    Or customized below -15 ºC, model is optional;
Chilling power:
    water-cooled unit: 10 ~ 400 kw
    air cooled unit: 8 ~ 120 kw, model is optional;
 
Monitoring equipment:
Usage: to save a certain period of video surveillance data, conveniently query, forensics, and provide the basis for future investigation.
 
Automatic fire alarm system:
At the beginning of the fire, the system can transfer physical quantities, including smoke, heat and radiation generated by combustion, through temperature sensor, smoke and photosensitive detectors, into electrical signals, and transmit to fire alarm controller, simultaneously display the position of the fire and record the happening time.
 


 WHOLE-ROOM AIR CONDITIONING DEVICE:

Temperature control range: 20 ~ 35 ºC; Control accuracy: ±2ºC;
Humidity control range: 40% ~ 70%; Control accuracy:±5% rh;
Lubricating total air volume: 20000m3/h~100000m3/h.
The whole-room air conditioning device integrates the fresh air intake system and air exhaust system, to realize full fresh air, full exhaust function and form indoor air convection. Air inlet and outlet are set on the top of the test room.

To form a micro negative pressure (10 ~ 50 pa)condition inside of the test room.
Other features: all the control signals can be transmitted to engine test bench console for real-time monitoring.